Rolling Steel Fire Door Guide

Guides · Fire doors

Automatic closing, fusible links, release devices, governors and drop testing. How a fire door proves it will close when nobody is standing there to close it.

Call 1-800-528-4131Request an inspection

Wilcox technician replacing a coiling fire door at a chemical distribution facility

A rolling steel fire door looks like any other coiling door until something goes wrong. What makes it a fire door is a label, and what makes that label mean anything is a release mechanism that closes the door without power, without a person, and at a speed that won’t injure anyone standing underneath. This guide covers how those mechanisms work, what they must have, and how they’re tested.

Who this guide is for. It is written for facility managers and maintenance teams who own and operate fire doors, so you know what a correct installation, test and record looks like and what to ask a contractor. It is not a training manual. Releasing spring tension, dropping a curtain and resetting a fire door are work for a company trained and certified in fire door drop testing, such as Wilcox. Nothing in this guide is advice to test or repair a fire door yourself.

The short answer

A fire door’s job is to close itself. It has to be labeled as an assembly, and it has to close automatically on a signal from a fusible link or a detector. The fusible link melts at about 165°F. The release must drop a portion of the counterbalance so gravity closes the door, and a governor holds the descent to roughly 6 to 24 inches per second. Every fire door needs inspection and drop testing, with the results documented.

Link melt point165°FTypical for door applications
Link position4-12 inBelow the ceiling, both sides
Closing speed6-24 in/sControlled by the governor
Test intervalAnnualPer NFPA 80, documented

1. What makes it a fire door

Three things, and all three have to be present. A fire door carries a label identifying it as a tested assembly for a stated rating. It is self-closing and stays closed once released. And it is installed in the opening with its hardware intact, because the rating belongs to the whole assembly: door, guides, hardware, release device and frame.

That last point is where most compliance problems live. A technician who removes a fusible link housing because it caught on a pallet, or who wedges a door open for airflow, hasn’t caused a maintenance issue. They’ve defeated the fire separation, and the door no longer performs the function it was installed for.

If you hear one thing from this page: a fire door is not a door with fire hardware bolted to it. It is a labeled system, and any field modification that isn’t permitted by the label puts the certification in question.

2. Two release families

Every automatic closing system has to do the same thing: stop holding the door up. There are two ways to arrange that, and knowing which one you’re looking at decides how a drop test is performed and what resetting involves.

Tension drop-off Non-spring release
What releases A portion of counterbalance spring tension A separate release mechanism; spring tension stays
How it closes Gravity, with the governor controlling speed Gravity via the release, speed controlled by the governor
Drop testing Actuate the release; the arm drops Floor-level disconnect simulates link activation
After a test Recharge the system and re-tension Reset the disconnect and the door returns to service

On a push-up fire door in the charged position, a dropout arm is held engaged by a sash chain or cable. A fusible link joins two sections of that chain. When the link melts, the chain separates, the drop arm releases, and part of the spring tension goes with it so the door falls closed under control.

1. Chargedarm held by sash chain link parts2. Link meltschain separates at 165F gravity3. Door closesgravity, governed speed

The release sequence. Once the link separates, nothing holds the arm and the door descends on its own, with the governor controlling the rate.

A fusible link is two metal pieces held together by solder that melts at a set temperature, typically around 165°F for most fire door applications. It is simple, needs no power, and works when everything else has failed. That’s also why its placement matters so much: a link that sits in dead air above a false ceiling will never see the heat it’s meant to respond to.

ceilingcoil sideopposite side4 to 12 in below ceilingdrop or false ceiling:link needs a housing

Links sit 4 to 12 inches below the ceiling on both the coil side and the opposite side, and near the door opening on the coil side.

  • Height. 4 to 12 inches below the ceiling, so the link sits in the hot gas layer that forms at the top of a room, not at head height.
  • Both sides. Coil side and opposite side, because heat does not reliably reach one elevation only.
  • Near the opening. Additionally required on the coil side, so a fire at the opening releases the door early rather than after the room is fully involved.
  • Housing. Where a drop or false ceiling exists above the opening, the link needs a housing that keeps it exposed to the heat it’s meant to detect.

Never paint, tape or bag a fusible link. Anything that insulates the link from the air delays it, and a delayed fire door is the same as a missing one in the minutes that matter. Links are replaced, not maintained.

A link carries its specification stamped on it: the manufacturer, the listing mark, the temperature rating, a pull rating and a date. Those markings are what an inspector reads, so a link with the stamp worn or painted off is already a finding.

Marking What it tells you The rule
Temperature The melt point of the solder 165°F is typical. 212°F is used in special cases
Pull rating A letter for the load the link carries The letter must match what the door manufacturer lists for the assembly. A link swapped for whatever was on the van is a finding
Listing UL or FM approval UL listings are in the UL Building Materials Directory under JGIX
Date When the link was made Some manufacturers recommend replacing once a year
  • Heat environment. A 165°F link has a recommended maximum exposure of 100°F. If the opening regularly runs hotter than that, step up to 212°F, otherwise the link can let go on a hot day.
  • Sprinklers. The link rating must be lower than the temperature rating of the sprinkler heads, and the link should be shielded from the head so it is not drenched.
  • FM-listed doors need FM links. Factory Mutual links differ from UL links. Fitting the wrong type on an FM-listed door can fail an inspection, stop the AHJ or FM inspector approving it, and void the FM rating.
  • Creep. A link under constant load slowly fractures (“cold flow”). It is why some manufacturers say to replace annually. NFPA 80 does not set a replacement interval, but it does require installation to the manufacturer’s instructions.

Links connect to the sash chain or cable with S-hooks and should sit at least 6 inches from any fixed point, such as a pulley, eyebolt or through-wall pipe, so they do not catch when they release. Where a drop or false ceiling hides the opening, the link needs a housing. All of the links on a door are interconnected, so separation of any one of them closes it.

Inspect links and routing annually, and more often in harsh conditions. Look for corrosion, cracks, paint or overspray, chemical residue, and stretched or frayed chain. NFPA 80 requires that a painted link be replaced. In salt, chemical or damp environments, replace links every year.

Sash chain and cable: the quiet failure

Twisted or snagged chain and cable is one of the most commonly reported reasons a conventional fire door does not close. The release only works if the chain runs free through every pulley, through-wall pipe and eyebolt when the link lets go.

Good routingfuse link, 6 in from any fixed pointgentle turns, pulley at each changeWill not dropsharp angle under 90 degreeskinks and snags stop the release

Gentle turns with a pulley at each change of direction release cleanly. Sharp angles and nearby fixed points snag.

  • Use chain and cable supplied by the original fire door manufacturer.
  • Plastic-coated wire rope should not be used.
  • Cable should be a nominal 1/8 inch or 3/32 inch diameter.
  • Avoid angles under 90 degrees, and keep the link’s travel path away from eyehooks, wall penetrations and obstructions.
  • Put turnbuckles above a height where they can be tampered with.

The AHJ has final approval of the link location and routing, so a layout that looks neat to the installer can still be rejected on inspection.

4. Electrical release devices

Where a door is tied to a fire alarm rather than relying only on heat at the door, a release holder takes the electrical signal from the panel, a smoke detector or a heat detector and converts it into a mechanical release. The same mechanism then runs: cable or chain releases, the door closes under the governor.

Thermal releasefusible linkmelts at about 165F, no power needed Electrical releasealarm or detectorrelease holderneeds standby power, or door drops on outage

A thermal link works without power. An electrical release depends on the signal arriving, so it must be able to fail safe.

The critical requirement is the power supply. A release holder needs a standby source, or the door must drop on any power outage. A release device that holds a door open through a blackout is holding a fire door open during a fire, and that is precisely the failure nobody plans for.

Signal pathPanel or detector to release holder, independent of the door operator
Fail safeStandby power, or the door releases on loss of power
Two devicesThermal link plus electrical release is normal on a protected opening

Four kinds of electro-mechanical release

Electrical release devices come in several configurations. The differences matter because they decide what happens when the alarm sounds, when the power fails, and when something is in the way.

Type What it adds Watch for
Basic release device Takes the panel or detector signal and releases the chain or cable Needs a backup power supply, or the door must drop on any outage
With battery backup On-board battery powers the release device only, for up to 72 hours Keeps the door “ready” in a power loss, but the battery does not run the operator
With backup and motor controller Closes the door with the motor on alarm, if the operator has power Needs an electric sensing edge for obstruction detection
Motor-controlled, non-spring release Motor, release and brake in one unit. Spring tension is never released If the motor has no power it releases an electric brake and the door closes by gravity
Alarm signalpanel or detectorPower to motor?yesMotor closes doorsensing edge watchesnoReleases, gravitygoverned descentObstruction?retry up to 3 timesStill blockedcloses onto it, or dropsWhat happens at the third attempt is selectable in the unit and set by the AHJ.

On alarm the door closes under power if it can, and by gravity if it cannot. A blocked door retries three times before it settles.

Two features are worth knowing about. The release can delay for up to 10 seconds after the signal (verify local code), which cuts nuisance drops from alarm blips and, more importantly, gives people and equipment near the door time to notice what is happening. And the obstruction logic reverses a blocked door, retries up to three times, and then either closes onto the obstruction or releases and rests on it. That final behaviour is selectable in the unit and is a decision for the AHJ.

Detectors that trigger the door

Where a door is tied to the fire alarm instead of relying only on heat at the opening, the detector and the release device have to be compatible. They must use Form C contacts, and where there are several detectors they are wired so that any one of them closes the door.

  • Photoelectric detectors measure light scattered by smoke. They can be fooled by theatrical effects or by areas that regularly see dense smoke.
  • Ionization detectors measure visible and invisible combustion particles. Vehicle exhaust and chemical vapours can trip them. Combined smoke and heat models exist.
  • Heat, rate-of-rise and CO2 detectors are available and can work alongside smoke detectors.
  • End-of-line relays are required by UL at the end of every smoke detector circuit. If power to the detectors is lost, the relay flips the circuit to alarm, so the door closes. Without it a dead detector looks exactly like a healthy one.
ceilingside wallnever hereceiling mount: 4 in or more from the walltop of detector4 to 12 in below ceilingFit detectors or links on BOTH sides of the wall,interconnected so any one device closes the door.

Smoke detectors mount on the ceiling at least 4 inches from the wall, or on the wall with the top of the detector 4 to 12 inches below the ceiling. Never in the corner triangle.

Detectors or links go on both sides of the wall, interconnected, except that detectors are not required on the exterior side of an exterior wall. Mounting is set by NFPA 80 and NFPA 72, and always by the manufacturer’s instructions first. Smoke detectors usually give no warning when they trip, so strobes, horns or voice annunciators are recommended where nothing else warns people, or where pedestrians and moving machinery are close to the door.

Detector wiring also decides how many doors drop. Tying detectors into the whole building alarm can drop every fire door at once, while grouping doors into local zones means only the doors in the affected zone close.

5. The governor and closing speed

Once the door is released it falls, and an ungoverned falling door is a hazard rather than a safety device. The governor limits the descent to somewhere between 6 and 24 inches per second depending on the door and design.

On some systems the operator itself acts as the governor, which gives finer control over the closing rate. Either way, the test is the same: the door has to travel at a speed that won’t injure a person in the opening, and it has to reach the floor and stay closed.

NFPA 80 states it directly: the closing speed must average no slower than 6 inches per second and no faster than 24. Fire rated doors from every manufacturer are designed to meet that, and the installer has to test the installation to demonstrate it for the AHJ. Note that this is a different figure from a motor operator’s normal running speed, which is typically 6 to 12 inches per second.

Non-spring doors are deliberately out of balance. Because they are built to drop when released, the curtain must be secured at all times during installation and service. If the brake or governor is disengaged or damaged, or sprocket alignment or chain tension is wrong, the door can free-fall and injure someone or wreck itself.

6. Inspection and drop testing

A drop test answers one question: if the release were triggered right now, would this door close fully, at a controlled speed, and stay closed? Nothing else proves it. A door can be balanced, quiet and serviceable and still fail to close because a link is painted over, a chain is seized, or a disconnect was never reset.

Have this done by a certified company, not in house. A drop test releases stored spring tension and drops a steel curtain. It is physically dangerous, it can damage the door if the sequence is wrong, and it is the piece of work most likely to injure someone who has not been trained on it. Fire door drop testing is a certified trade: use a partner trained and certified in it, such as Wilcox. Your job is to know when it is due, witness it if you can, and keep the paperwork.

At installationRequiredNFPA 80
IntervalAnnualAt least, per NFPA 80
After serviceEvery timeAny time the door is serviced
Records kept3 yearsAvailable to the AHJ

What a certified test involves

The sequence below is what a qualified technician performs, and what you should expect to see if you are present. It is here so you can tell a thorough visit from a quick one.

1. Visual inspectionguides, links, chain, power2. Operational checkfull cycle, smooth, no strain3. Drop testfrom full open onlyDrop #2proves resetfail either check: repair first, never drop test a defective doorThe three-step test

Two inspections come before any drop. A door that fails either one is repaired first, because dropping a defective door risks damage and injury.

Step 1: visual inspection

The whole assembly is checked before anything moves. This is where most problems are found, and finding them here is cheaper and safer than finding them during a drop.

Area What is confirmed
The door generally Nothing attached to the door, the opening clear of obstructions, curtain, barrel and guides plumb and level, and every part from the original manufacturer
Guides Wall fasteners present and tight, no gaps between wall angles and jambs, welds and weld locations per the manufacturer, expansion allowance correct with fasteners in the proper slot positions, guides not pinched, bent, loose or full of debris
Brackets and operating mechanism No worn, missing or misaligned parts, no missing gear or sprocket teeth, no bent shafts
Links, release devices, detectors, chain and cable Release and drop arms properly connected, located per NFPA 80, local code and the manufacturer, links not painted (replace) and not coated in dust or grease, cable not kinked or pinched, sash chain flexible and untwisted, raceways and eyelets clear, smoke detectors and auxiliary devices powered, and the release mechanism not tied off to prevent closing

Step 2: operational inspection

The door is run through a complete cycle to confirm it moves smoothly. Signs of a broken spring are excessive lift effort, excessive hoist effort, or a struggling operator. Any abnormal noise or damage is investigated and repaired before anything is dropped.

Step 3: the drop test

The drop is only performed once both inspections have passed and the door is believed free of defects. On the day, expect the technician to do the following, and expect to be asked for a witness:

  1. Open the door fully. A drop test is never done from any position other than full open.
  2. Rope off the area and notify people nearby that a drop test is under way. Clear anything stored under or near the door first.
  3. Arrange a witness from the building owner, the owner’s agent, or the AHJ. Ideally that is someone on your team.
  4. Secure anything that can spin or swing. On fire doors the awning crank handle comes off, and hand chains and other movable items are secured.
  5. Initiate the drop by inducing slack in the sash chain or cable, or by activating the alarm.
  6. Time it and watch the finish. The door must close completely, in full-width contact with the floor, sill or countertop, at the right speed.
  7. Reset the release devices and verify the door operates.
  8. Drop it a second time to confirm the reset worked. A single drop only proves half of what matters.

Never try to stop a moving door once a drop has started, and never operate the release yourself to “see if it works”. If a door does not fall when the release is operated, it must be secured against falling immediately and a trained door systems technician called. A door stuck in the open position with a compromised release is a door that will not close in a fire.

How drop speed is measured

Drop speed formulaheight (in) / secondsfrom release until the door contactsthe floor, sill or countertop10 ft = 120 in, in 10 s= 12 in/sAcceptable range624too slowtoo fastpassinches per second, door must alsoseat in full-width floor contact

The opening height in inches is divided by the seconds from release until the door contacts the floor, sill or countertop. The result must fall between 6 and 24 inches per second.

Ask for the number. A measured speed in that range, written on the report, tells you the governor and counterbalance are doing their jobs. “Tested and passed” with no figure is not the same thing.

Every means of activation gets tested

NFPA 80 requires testing by all means of activation, repeating the drop as needed so every release device and location is proven. A door that drops from its floor-level disconnect has not necessarily been proven to drop from its alarm signal, and an alarm-path failure is the one that matters in a real fire.

Test every means of activationMelt a fusible linksometimes required by the AHJSeparate a turnbucklesimulates link separationCut power to the releaseelectro-mechanical devicesTrip the building alarmproves the signal pathNFPA 80 requires testing by all means of activation, repeating as needed so every release device is proven.

A door with a thermal link and an electrical release needs both paths tested.

The paperwork to ask for

Most new doors ship with a drop test form, and manufacturers supply them. It is completed whenever a drop test or inspection is performed, and it is kept on record for AHJ inspection for three years. One copy stays with the door, one with the installer or dealer, and one with you. Keep your copy somewhere you can find it when an inspector or insurer asks, not in the maintenance van.

Do not witness your own test. The witness should not be from the company doing the work. If your own staff cannot attend, ask the AHJ or a third party. A drop test signed off only by the firm that performed it is weaker evidence than one witnessed independently.

When a door should be replaced rather than tested

Not every door should be serviced, and a reputable company will tell you so. The industry guidance (DASMA TDS 257 and 275) sets out the situations where testing and servicing should be declined altogether. If a contractor agrees to test a door in the first three rows below, that is a warning sign about the contractor.

Situation What should happen
The door is modified or damaged and cannot be repaired with parts from the original manufacturer The door is not serviced or drop tested. Replacement is recommended
The door is no longer made and original parts are unavailable, or the manufacturer is out of business The door is not serviced or drop tested. Replacement is recommended
The door has sustained unrepairable damage The door is not serviced or drop tested. Replacement is recommended
The company lacks the information, the original parts, or the qualification to service it properly Servicing is declined, and another qualified firm is recommended
The door is undamaged, needs only routine maintenance, or every repair can use original-manufacturer parts, and the firm has the expertise Service and drop testing proceed

Repairs are made and defects corrected without delay, with parts from the original manufacturer. Labeled retrofit options may exist for the operator and automatic closing device if the AHJ approves, and a retrofit operator may come from another manufacturer if it is listed. Field modifications must be approved by the listing agency, the manufacturer and the AHJ, and a field inspection may be required. Every repaired fire door is drop tested, at least twice, and a written record is kept including the witnesses.

Bottom bars have a special provision worth knowing about, because it is a common shortcut. A replacement must come from the original manufacturer under the listing agency’s follow-up service procedure: the original label goes back to the manufacturer, who supplies a new bottom bar with a new label. A bottom bar fitted from stock, with no label, has broken the certification of the door.

About the floor-level disconnect

Many doors have a floor-level disconnect, which allows the release to be tripped without tools or a ladder. It exists so the door can be tested more often than the annual visit, but “easier to test” is not the same as “safe for anyone to test”. The stored energy in the door does not change, and the failure mode of a mis-sequenced drop is an uncontrolled curtain.

  • Treat it as a device for a trained technician, not a maintenance shortcut.
  • If your insurer or AHJ expects more frequent testing than annually, schedule more frequent visits from your certified partner rather than performing them in house.
  • Keep the disconnect secured against unauthorised use, and never activate it on a damaged door or while the door is moving.
  • Always two drops in a row, which is a trained sequence, not a quick check.

If a drop test fails

The table below is what a technician will be looking at. It is useful in a report, and useful when you want to understand why a door was condemned, but the adjustments are technician work.

What is seen Likely cause and correction
Drop speed too fast or too slow Adjust spring tension (add for faster, remove for slower), or inspect and adjust a malfunctioning governor
Door does not drop when tested Improper sash chain or cable routing, or a bound curtain: check that the flame baffle is not rubbing the curtain and the curtain is not rubbing the guides
Door does not operate at all Release lever disengaged: check chain or cable routing
Door sticks when closing Inspect for bent or kinked guides and straighten, and verify the guide opening measurement
Curtain runs to one side Broken endlocks (replace), barrel not level, or slat misalignment
Hard to open but closes easily, or does not stay open Add spring tension
Hard to close but opens easily, or jumps up from the floor Reduce spring tension

Booking the annual test

Three things make the annual visit painless: know the inventory, know the date, and know who is allowed to do the work. Ask any provider for their fire door drop testing certification before they touch a door, ask for the measured drop speed on the report, and keep the signed form for three years. If a door has been painted, altered, propped or tied off since the last visit, say so when booking, because it changes what the technician has to check.

Wilcox performs certified fire door drop testing across rolling steel and coiling fire doors, all makes and models, with the written report your insurer and fire department ask for. If you are not sure when your doors were last tested, that is the call to make today.

7. Resetting after activation

After a genuine activation or a drop test, the door has to be returned to service properly, and the sequence differs by release family.

Situation What has to happen
Floor-level disconnect tripped Reset the disconnect, which returns slack to the sash chain and restores normal operation
Fusible link melted The link is replaced; a melted link cannot be reset, and substituting anything else defeats the door
Tension drop-off door The released spring tension has to be recharged and re-tensioned before the door will operate normally
Electrical release fired Reset the release holder and restore the signal path, then verify the door responds to both the panel and the thermal link

Resetting a tension drop-off door (technician procedure)

Doors that release spring tension take the longest to put back, and it is not a job for guesswork. The sequence below is what a trained technician follows, and it is here so you understand why a reset can take time and why it is not something to attempt in house. Manufacturers differ and their written instructions always take precedence.

  1. Raise the door fully open and clamp it in the guides so it cannot fall.
  2. Reapply spring tension to the manufacturer’s specification until the door stays open on its own.
  3. Engage the dropout arm and reconnect the sash chain or cable.
  4. Replace any melted or damaged links and restore the chain to its original configuration.
  5. Remove the clamps and operate the door several times to confirm smooth running.

On motorized doors you may need to run the motor to the fully closed position first, to resynchronise the limit switches, then reopen and clamp. Electrical activation components are reset as the manufacturer describes.

Resetting a non-spring release door (technician procedure)

Because spring tension is never released, this is much easier and safer. Electrical systems often just need the alarm cleared and power restored, then the door run open with the operator. On manual systems you restore the links or reset the chain or cable to its armed state and open the door. Some motor-controlled units will not open after an alarm until the operator is reset with a key.

A door left in a released state after a test is a door that will not close in a fire. Whoever performs the test owns the reset.

8. Operating a fire door day to day

A fire door still has to work as a door, which is where the day-to-day compromises creep in.

  • Direct drive is rarely used on fire doors. The operator has to disengage so the door can close on its own, which is why chain hoist and similar arrangements are common.
  • Chain hoists on fire doors must allow the hoist to disengage, or automatic closing can’t happen at all.
  • Hold-open is not a feature, it’s a violation unless it’s an approved release device that lets go on alarm.
  • Emergency egress doors, typically rolling grilles, are a different design: over-sprung so they open on their own when the operator is released, with the operator’s internal resistance acting as a brake.
  • Blocked openings are the common failure. Pallets stacked in the opening, a chain padlocked through the curtain, or a disabled release are all the same problem with different appearances.

9. Installing and specifying a fire door correctly

A fire door that is specified wrongly or fastened to the wrong wall cannot be rescued by good hardware. Most of the errors that surface at inspection were made before the door arrived. This section is here so you can judge whether the company installing your doors is doing it properly, and so your own specification and site conditions hold up their end.

Read the specification first

The bid specification usually carries the installation, safety and documentation requirements, not just the door description. It normally states the rating and class, who prepares the opening, the acceptable manufacturers (and any “or equal” clause), the curtain, guides, counterbalance, brackets and hood, the operation type, and the closing devices. Closing devices are often the most difficult part to interpret, because architects rarely state more than “must close”.

The specification will also commonly demand a drop test, sometimes witnessed by a representative of the end user, and may require an installer with a stated number of years of experience. Use a drop test form signed off by the customer or AHJ and by the technician.

  1. Request shop drawings from the manufacturer before ordering, then review and field-verify them.
  2. Get written approval on the drawing from someone with authority to approve. If anything changes, reissue the drawing for re-approval.
  3. Send the signed drawings with the order. That extra check prevents errors and disputes.
  4. Check the delivery. Verify piece count and condition, note any damage on the shipping documents before signing, and store the product indoors, especially electrical parts and special finishes.
  5. Install to the manufacturer’s written instructions. The training guidance is explicit that general references are not a substitute, and that modifications are not permitted.

What the opening has to be made of

The rating of a fire door depends on what the guides are fastened to. The listed jamb details specify minimum fasteners of 3/8 inch diameter, edge distances measured as multiples of the bolt diameter (6 times from either edge, 8 times into the masonry), and a minimum 2500 psi concrete or brick.

Wall type What the details require
Filled CMU block Cores filled with at least 2500 psi concrete, with rebar in the filled cores
Brick or poured concrete Minimum 2500 psi, with rebar; bolts at least 8 bolt diameters in from the edge
Steel jamb (angle, channel or bent plate) Minimum 3/16 inch steel with welded studs, embedded or secured to the masonry
Metal stud wall Minimum 14 gauge stud, or a 3/16 inch steel tube, with gypsum thickness set by the wall rating
Existing rated wall A steel tube set against the face of the wall, with an inner sleeve and a 1/8 inch maximum clearance

Steel members have to be allowed to expand in a fire. The listed details call for an expansion gap of 1/8 inch for each foot of opening height where a guide angle is welded to a steel jamb, and metal shims between the guide wall angle and the wall where the steel stops at the header. Unfilled block can be used only with a threaded rod and crush plate arrangement, not with a simple surface fastener.

Check the wall before you order the door. A rated opening that does not match one of the listed jamb details will not carry the label, however good the door is. Confirm the construction on site and compare it with the manufacturer’s details for the specific rating.

What a competent installer does on site

  • Paperwork and parts. Check the paperwork, verify every crate and component against the manufacturer’s parts list, and review the instructions and drawings for the door and any accessories.
  • Site rules. Many sites need specific PPE, safety training or hot work permits. Notify other trades and secure the opening area.
  • Assess the opening. Jambs must be plumb, level and square. When removing an old door, clear old welds and debris and finish repairs first. It is the installer’s job to verify the wall suits the fire rating and can carry the door’s weight, and to tell management about any discrepancy, because staying silent increases exposure to door failure and liability.
  • Space. Verify the opening, clearances and side room against the approved shop drawing. Fire doors usually need extra headroom for release cable runs, electrical release devices, fuse links, pulleys, eye bolts and the dropout mechanism.
  • Future trades. HVAC, communications or cranes added later must not impede the door closing. Nothing can be attached to the door and nothing stored where it could block it.
  • Hardware. For fire rated products the hardware must come from the manufacturer. If it cannot be used, any substitute must be approved by the manufacturer.

Guides, expansion and fasteners

Proper guide installation gives smooth operation, reliable drop-outs and agency compliance. Guide spacing must follow the installation manual and the guides must be plumb. If either is wrong, the fire and wind load ratings may be void, and the manufacturer should be contacted any time field conditions differ from the approved drawings.

  • Measure the floor slope and shim as required.
  • With downward guide expansion, shim both guides off the floor.
  • With upward expansion, leave adequate space above the guide mounting angle.
  • Fasteners must sit in the specified locations within the mounting slots, using the supplied washers and fasteners.

Hanging the curtain and setting tension

Smaller doors can have the curtain rolled onto the barrel on the floor. Larger doors are slung to reduce the lifting weight, with the tension end of the barrel, which holds the springs, treated as the heavier side when placing straps. Whichever method is used, the barrel has to be level, the coil restrained from unrolling, and the bottom bar fed into the guides and clamped before the stops go on.

Use extreme caution applying spring tension. Use correctly sized winding bars, apply tension in the direction the door would turn as it coils up, wind in the up position for the least tension, and apply only enough to hold the door up. Adjustments should be made only by trained, experienced people.

Finish with the hood, including intermediate supports where required, and test the flame baffle if the door has one. Then fit guide and lintel seals, the tension and drive covers, and the safety and warning labels, clean up, and perform the witnessed second drop test and the form.

Relocating an existing fire door

Moving a rated door to a new opening is possible but not casual (DASMA TDS 285). The original label or certificate must be found, the door size cannot be field modified, the wall construction must match with the listed guide fasteners, and the rating has to be right for the new opening. Fusible link changes need original-manufacturer parts, and release devices must be compatible with the new alarm system. Check leakage rating requirements where they apply, the door’s age and condition, and whether installation instructions and drawings still exist. The AHJ has the final say on approval, including what happens to the old opening if it is abandoned, replaced or left open.

Fire door not tested this year?

We inspect, drop test and document rolling steel fire doors, and we service all makes and models. If a door has been propped, painted over or modified, we’ll tell you what it takes to get it back to a compliant state.

Request an inspection Call 1-800-528-4131

Rating classes, label requirements and the wider compliance picture are covered on our fire door ratings page and fire door overview. For the general anatomy of a coiling door that isn’t fire rated, see the rolling steel door guide.

Frequently asked questions

How does a rolling steel fire door close without power?

It releases stored counterbalance energy and lets gravity close the door. A fusible link melts at about 165F and separates a sash chain, which releases a drop arm. A governor then holds the descent to roughly 6 to 24 inches per second.

Where should a fusible link be located?

Four to twelve inches below the ceiling, on both the coil side and the opposite side of the door, and additionally near the door opening on the coil side. Where a drop or false ceiling exists, the link needs a housing so it stays exposed to heat.

What temperature do fusible links melt at?

About 165F for most fire door applications. The solder in the link is designed to let go at a set temperature rather than relying on any electrical signal.

How fast should a fire door close during a drop test?

Six to twenty-four inches per second, controlled by the governor. What matters is a smooth, controlled descent that seats fully. A door that slams is failing the test even if it ends up closed.

How often do fire doors need to be tested?

NFPA 80 sets the inspection and testing requirements, and drop testing is required at installation, at least annually, and whenever the door is serviced. The test itself is certified work: it is performed by a company trained and certified in fire door drop testing, such as Wilcox, with an independent witness and a signed record. Your AHJ sets what is accepted locally.

Can a fusible link be painted or replaced with wire?

No. Paint insulates the link and delays it, and wire or any substitute defeats the release entirely. A melted link is replaced with the correct part, never repaired.

What is a fusible link pull rating?

A letter stamped on the link showing the load it is designed to hold, and it must not be exceeded. The correct link for a given door is the one the manufacturer lists for that assembly, so the letter is checked against the door, never swapped for whatever is in the van.

When should a 212F link be used instead of 165F?

Where an opening regularly runs hot, such as above a process or near heating equipment. A 165F link assumes a normal ambient temperature at the opening, so a hotter location takes a higher-temperature link such as 212F. The manufacturer’s listing for that door decides the correct one, and the link always stays rated lower than the sprinkler heads serving the area.ower than any sprinkler heads.

Can a fire door release be delayed after the alarm?

Yes. An electro-mechanical release can delay up to 10 seconds, subject to local code. It reduces nuisance drops from alarm blips and gives people and equipment near the door time to react.

What is an end-of-line relay on a smoke detector circuit?

A relay UL requires at the end of every smoke detector circuit. If power to the detectors is lost, it switches the circuit to alarm so the door closes, instead of a dead detector looking healthy.

Why is a fire door drop tested twice?

The first drop proves the door closes fully at the right speed. The second proves the automatic closing device was reset properly. A door that only passes once has not been shown to be ready for service.

Who can witness a drop test?

The building owner, the owner's agent, or the AHJ. The witness should not be from the company that installed or inspected the door. Do not witness your own test.

How do you calculate fire door drop speed?

Divide the opening height in inches by the seconds from release until the door contacts the floor, sill or countertop. A 10 foot door is 120 inches, so 10 seconds is 12 inches per second. It must fall between 6 and 24.

Can any fire door be repaired?

Only with parts from the original manufacturer. If the door is modified or damaged beyond repair, the parts are unavailable or the manufacturer is gone, the right recommendation is replacement rather than service or a drop test.